Publication 1762-IN006C-EN-P - September 2009

Working Voltage

Turn-On Time (maximum)

0.1 msec

6 µsec

Turn-Off Time (maximum)

1.0 msec

18 µsec

Repeatability (maximum)

n/a

2 µsec

Drift (maximum)

n/a

1 µsec per 5°C (9°F)

(1)

Output 2 is designed to provide increased functionality over the other FET outputs. Output 2 may be used like the other FET
transistor outputs, but in addition, within a limited current range, it may be operated at a higher speed. Output 2 also
provides a pulse train output (PTO) or pulse width modulation output (PWM) function.

Description

1762-L24AWA, 1762-L40AWA, 1762-L24AWAR, 1762-L40AWAR

Power Supply Input to
Backplane Isolation

Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second

265V ac Working Voltage (IEC Class 2 reinforced insulation)

Input Group to Backplane
Isolation

Verified by one of the following dielectric tests:1517V ac for 1 second or 2145V
dc for 1 second

132V ac Working Voltage (IEC Class 2 reinforced insulation)

Input Group to Input Group
Isolation

Verified by one of the following dielectric tests:1517V ac for 1 second or 2145V
dc for 1 second

132V ac Working Voltage (basic insulation)

Output Group to Backplane
Isolation

Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second

265V ac Working Voltage (IEC Class 2 reinforced insulation)

Output Group to Output
Group Isolation

Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1second

265V ac Working Voltage (basic insulation) 150V ac Working Voltage (IEC Class
2 reinforced insulation).

Description

General Operation

High Speed Operation

(1)

(Output 2 Only)