Rockwell Automation 1769-XXXX Compact I/O Modules User Manual
Page 106

106
Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
Chapter 3 I/O Memory Mapping
Configuration Data File
To select
Make these bit settings
15 14 13 12 11 10 9
8
7
6
5
4 3 2
1
0
Filte
r Freq
ue
ncy
10 Hz
Not Used
(1)
(1) An attempt to write any nonvalid (spare) bit configuration into any selection field results in a module
configuration error.
1
1
0
60 Hz
0
0
0
50 Hz
0
0
1
250Hz
0
1
1
500 Hz
1
0
0
1 kHz
1
0
1
O
pen-
cir
cu
it
Upscale
0
0
Downscale
0
1
Hold Last State
1
0
Zero
1
1
Te
m
p.
°C
0
°F
1
Input T
ype
Thermocouple J
0
0
0
0
Thermocouple K
0
0
0
1
Thermocouple T
0
0
1
0
Thermocouple E
0
0
1
1
Thermocouple R
0
1
0
0
Thermocouple S
0
1
0
1
Thermocouple B
0
1
1
0
Thermocouple N
0
1
1
1
Thermocouple C
1
0
0
0
-50…50 mV
1
0
0
1
-100…100 mV
1
0
1
0
Da
ta
Fo
rmat
Raw/Proportional
Data
0
0
0
Engineering Units
0
0
1
Engineering Units x
10
1
0
0
Scaled-for-PID
0
1
0
Percent Range
0
1
1
En
ab
le
Disabled
0
Enabled
1