Channel configuration words – Rockwell Automation 1769-XXXX Compact I/O Modules User Manual
Page 131

Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
131
I/O Memory Mapping Chapter 3
Channel Configuration Words
Words 0 and 1 of the configuration file allow you to change the parameters of
each channel independently. For example, word 0 corresponds to channel 0.
Define
These bit settings
Indicate this
15
14
13
12
11
10
9
8
4…
7
3
2
1
0
Program
(Idle) to
Fault
Enable
Not Used
Not Used
0
Program (Idle)
Mode Data
Applied
(1)
(1) These functions are not supported by all controllers, such as MicroLogix 1500, using any configuration method.
Refer to your controller manual for details.
1
Fault Mode Data
Applied
(1)
Not Used
(Reserved)
Program
(Idle)
Mode
0
Hold Last State
(1)
1
User-Defined
Value
(1)
Fault
Mode
0
Hold Last State
(1)
1
User-Defined
Fault Value
(1)
Output
Range
Select
0
0
0
0
-10V dc to +10V dc
0
0
0
1
0 to 5V dc
0
0
1
0
0 to 10V dc
0
0
1
1
4 to 20 mA
0
1
0
0
1 to 5V dc
0
1
0
1
0 to 20 mA
Spare
(2)
(2) Any attempt to write a nonvalid (spare) bit configuration into any selection field results in a module
configuration error.
Output
Data
Select
0
0
0
Raw/Proportional
Data
0
0
1
Engineering Units
0
1
0
Scaled-for-PID
0
1
1
Percent Range
Spare
(2)
Enable
Channel
1
Enabled
0
Disabled