Rockwell Automation 1769-XXXX Compact I/O Modules User Manual
Page 49

Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
49
Module Wiring Chapter 2
External resistors are required if they are not internal to the encoder. The pull-up resistor (R) value
depends on the power supply value. To calculate the maximum resistor value, use this formula:
where:
·
R = maximum pull-up resistor value
·
Vdc = power supply voltage
·
Vmin = 2.6V DC
·
min = 6.8 mA
Single-ended Encoder Wiring
A
B
Z
A1(+)
A1(–)
B1(+)
B1(–)
Z1(+)
Z1(–)
GND
VS
+VDC
COM
R
(2)
Cable
Power
Supply
Allen-Bradley
845H Series
single-ended
encoder.
Shield/Housing
Connect only if housing is electronically
isolated from the motor and ground.
Shield
Module Inputs
Earth
Use twisted-pair, individually-shielded cable with
a maximum length of 300 m (1000 ft).
Power Supply Voltage
Pull-up Resistor Value Max (R)
(1)
(1)
Resistance values may change, depending upon your application.
5V DC
352
Ω
12V DC
1382
Ω
24V DC
3147
Ω
R
V
d
c
Vmin
–
(
)
Imin
--------------------------------------
=