Rockwell Automation 1769-XXXX Compact I/O Modules User Manual
Page 121

Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
121
I/O Memory Mapping Chapter 3
Program Value Word
The program value word, word 2, is used to program the user-defined safe state
condition. Each output is individually configurable for on or off.
Fault State Word
Word 3, the fault state word, selects the hold last state or user-defined safe state
condition on a system transition from Run to Fault.
Fault Value Word
The fault value word, word 4, is used to program the fault state condition. Each
output is individually configurable for on or off.
Program to Fault Enable Bit (PFE)
Word 0, bit 0, allows the selection of which data value, the program or fault value,
to apply to the output if a system in Program mode undergoes a system fault,
resulting a change to Fault mode.
Condition
Bit Setting
Off
0
On
1
Condition Bit
Setting
User-defined Safe State
0
Hold Last State
1
Condition
Bit Setting
Off
0
On
1
Value Applied
Bit Setting
Program
0
Fault
1