I/O Memory Mapping Chapter 3
The bits are defined as follows:
• Shaded bit positions must be set to 0.
• Input filter: Real input point filter selection. See page
190
.
• EI_Ix: Enable input interrupt; 1 = interrupt enabled, 0 = interrupt
disabled.
• IT_Ix: Input interrupt type; 1 = generate interrupt on real input point
transition from on to off, 0 = generate interrupt on real input point
transition from off to on.
• PFE: Program to fault enable; 1 = fault value applied, 0 = program value
applied.
• PMx: Program mode; 1 = hold last state, 0 = user-defined safe state.
• PVx: Program value; 1 = output on, 0 = output off.
• FMx: Fault mode; 1 = hold last state, 0 = user-defined safe state.
• FVx: Fault value; 1 = output on, 0 = output off.
• DB_x: Output Control; 1 = output in Direct Control mode, 0 = output
in BOOLEAN Control mode.
21
Output Delay 1
22
Output Duration 1
23
24
IT_O2
EI_
O2
DB
_1
25
Operand_A_2
26
Operand_B_2
27
Operand_C_2
28
Operator
_2_2
Operator
_1_2
29
Output Delay 2
30
Output Duration 2
31
32
IT_O3
EI_
O3
DB
_3
33
Operand_A_3
34
Operand_B_3
35
Operand_C_3
36
Operator
_2_3
Operator
_1_3
37
Output Delay 3
38
Output Duration 3
39
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0