Rockwell Automation 1769-XXXX Compact I/O Modules User Manual
Page 190

190
Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
Chapter 3 I/O Memory Mapping
• EI_Ox: Enable output interrupt; 1 = interrupt enabled, 0 = interrupt
disabled.
• IT_Ox: Output interrupt type. See page
191
.
• Operand_A_x: BOOLEAN operand A. See page
191
.
• Operand_B_x: BOOLEAN operand B. See page
191
.
• Operand_C_x: BOOLEAN operand C. See page
191
.
• Operator_1_x: BOOLEAN operator 1. See page
193
.
• Operator_2_x: BOOLEAN operator 2. See page
193
.
• Output delay x: Delay time from BOOLEAN expression transition from
false to true until output directed to transition from off to on. See page
194
.
• Output duration x: Pre-determined output pulse duration time. Time
from output directed to transition from off to on until output directed to
transition from on to off. See page
195
.
Wo
rd
Bit Position
(1)
(1) Darker shaded bit positions must be set to 0.
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0
Input
Filter
8 ms
0
0
0
0 s
0
0
1
100 µs
0
1
0
200 µs
0
1
1
500 µs
1
0
0
1 ms
1
0
1
2 ms
1
1
0
4 ms
1
1
1