Red

DUPL
NODE

For a redundant system this may
be a temporary condition during
chassis switchover. Otherwise,
the module’s network address is
the same as another module’s on
the link.

1. (For redundant systems only.)

Wait 10 seconds; if the
condition persists, perform the
following steps:

2. (Optional, see page 11.)

Turn chassis power supply off.

3. Remove the module from the

chassis.

4. Set the network address

switches to a unique address
(01-99).

5. Install the module in the

chassis.

6. If off, turn chassis power

supply on.

RACK
ERR

Cannot read backplane EEPROM,
or rack/slot address incorrect

Replace the chassis.

STOP

CNB commanded to stop
functioning by the redundancy
module. This occurs when a
non-redundancy compliant CNB
is placed into a redundant
secondary chassis.

Remove non-redundancy
compliant CNB from redundant
secondary chassis and replace
with redundancy compliant CNB.

WAIT
RM

CNB waiting for the redundancy
module to complete power-up.

None required.

Flashing
Red

BOOT

Module has invalid firmware.

Update module firmware with
ControlFlash Update Utility.

ROM
UPDT

Flash update is in progress.

None required.

SNGL
KPR!

Module detected that it has
been connected to a Cnet 1.5
(single-keeper) network.

Update the CNB module’s
firmware at MAC ID 01 and
reschedule the network.

Diagnostics

LED

Display

Cause

Action

OK