Controlnet channel status indicators – Rockwell Automation 1756-CNB ControlLogix ControlNet Bridge Module Installation Instructions User Manual
Page 26
 
26
Publication 1756-IN571B-EN-P - April 2001
ControlNet Channel Status Indicators
The ControlNet channel status indicators appear in one of the 
following states:
• steady - indicator is on continuously in the defined state.
• alternating - the two indicators alternate between the two 
defined states at the same time (applies to both indicators 
viewed together). The two indicators are always in opposite 
states, out of phase.
• flashing - the indicator alternates between the two defined
states (applies to each indicator viewed independent of the 
other). If both indicators are flashing, they must flash together, 
in phase.
Green or 
Off
SO_1
Old primary switchover phase 1 
in progress.
If the display shows any message 
for more than three seconds, then 
the CNB module failed during 
transition from one redundancy 
phase to another. Replace one or 
both redundancy modules.
SO_2
Old primary switchover phase 2 
in progress.
SO_3
Old primary switchover phase 3 
in progress.
SN_1
New primary switchover phase 1 
in progress.
SN_2
New primary switchover phase 2 
in progress.
SN_3
New primary switchover phase 3 
in progress.
?Cpt
CNB has not determined if it is 
compatible.
!Cpt
CNB has determined that it is 
not compatible.
Replace the CNB module with 
correct type and revision.
(1)
If switches are set to 00 the display scrolls “FAULT: ADDRESS SWITCHES = 00, ILLEGAL”
If switches are set to 99 in a redundant chassis, the display scrolls: “FAULT: ADDRESS SWITCHES = 
99, ILLEGAL IN REDUNDANT SYSTEM”
Diagnostics
LED
Display
Cause
Action
OK