Rockwell Automation 1756-CNB ControlLogix ControlNet Bridge Module Installation Instructions User Manual

Page 25

Advertising
background image

25

Publication 1756-IN571B-EN-P - April 2001

Green

OK

Normal operation

None required

INIT

Module is initializing.

BW
>MAX

Module is receiving too much
network traffic and connections
are timing out. The network
bandwidth has been exceeded.

None require (temporary
condition).
If this happens frequently, add
another 1756-CNB or -CNBR and
split the traffic between them.

CMPT

Secondary CNB is compatible
with its partner.

None required.

DSNP

Secondary CNB is disqualified
with no partner.

Check corresponding slot of
primary chassis for type and
revision of module.

PwDS

CNB is primary with a
disqualified secondary partner.

Check the type and revision of the
1756-CNB module.

PwQg

CNB is primary with a qualifying
secondary partner.

Redundant system status. No
action required.

PwQS

CNB is primary with a qualified
secondary partner.

PwNS

CNB is primary with no
secondary partner.

Check corresponding slot of
secondary chassis for correct
module.

Qfng

Secondary CNB is qualifying.

Redundant system status. No
action required.

QS

Secondary CNB is qualified.

SW
ERR

Node address switch changed
after power-up.

None required, but we recommend
that you either return switches to
their original settings or replace
the module, since this could
indicate a latent hardware
problem.

Flashing
Green

CNFG
ERR

ControlNet configuration error.

Recheck configuration.

NET

ERR

Network cabling error or no
other active nodes on network.

Re-check your network cabling
and make sure another node on
the network is active (on line).

Diagnostics

LED

Display

Cause

Action