Chapter 1 Import and export logic components

4. (Optional) In the File description, edit the default description or type a

description, if desired.

A default description is supplied for some component exports.

Tip:

The file description can be viewed in a tooltip during import when selecting which file to import.

5. Click Export.

This section covers general considerations for all component-type imports. See the

chapters for specific components (program, routine, rungs, Add-On Instructions,

user-defined data types, and tags) for additional export and import considerations

for that component, whether it is imported directly or as a reference during

another component import.

Important: When editing online, if the program scan time is large, or the number of modified rungs is large, you might

see HMI and Logix Designer communication timeouts when edits are finalized.
The timeout is caused by the (scan time) x (number of changed rungs). You could have a large program with
a very fast scan, or a lot of rungs (but you modified only a few), and you do not see a timeout.

Tip: Starting with version 24 of Logix Designer application, you can use program parameters to share data between

programs in much the same way that you use controller-scoped tags. Program parameters are imported and
exported in the same way as tags in most instances. For more information on program parameters, see the

Logix5000 Controllers Program Parameters Programming Manual,

publication

1756-PM021

.

Online Import

Topic

Consideration

Tag data values

When overwriting tags while online, data values are not written to the online project. Data

values for overwritten tags while online are written only to the offline project.
Data values for tags created while online are written to the offline and online project.
Select the Preserve existing tag values in offline project check box to prevent tag values
from being overwritten in the offline project.

Locking controller edits

When performing an online import, the controller is locked, preventing other workstations

connected to the controller from making edits until the import completes. If another
workstation has the controller locked, an online import cannot be initiated.

Tag attributes

Tag attributes (for example, External Access, Constant, and Style) are written to the online

project and the offline project.
If existing tags are to be overwritten with new attributes that are incompatible with existing
user logic, the import is not allowed.

Import considerations

12

Rockwell Automation Publication 1756-PM019E-EN-E - October 2014