24 ControlLogix ControlNet Interface Module

Publication

1756-IN604A-EN-P - February 2006

Interpret the Module Status Indicator and Display

The Module Status Indicator LED and Module Status Display table provide
diagnostic information.

Module Status Indicator LED and Module Status Display

LED

Display

Cause

Action

Off

None

The module is not
communicating due to a power
supply fault or internal fault.

1. Check the power supply.
2. Check the cable connectors.
3. Make sure the module is firmly

seated in the chassis.

4. If the indicator remains off,

replace the module.

Red

Msg

scrolls

(1)

The module’s network address is
set to 00, an invalid ControlNet
network address, or 99, an
invalid ControlNet network
address if you are using
redundant control. See footnote
at end of table.

1. (Optional, see page 12.)

Turn chassis power supply off.

2. Remove the module from the

chassis.

3. Set the network address

switches to a unique address
(01-99, or 01-98 if redundant
control)

4. Install the module in the

chassis.

5. If off, turn chassis power

supply on.

BPA#
ERR

The module detected a different
slot address from that latched in
at power-up. Excessive noise on
the backplane causes this error.

Replace the chassis or module.

BPRX
ERR

There are too many CRC errors
being generated by the multicast
backplane receiver, so the
backplane multicast receivers
have been shut off.

Replace the module.

BPIC

ERR

There is a hardware fault

within the module.

Replace the module.

CNIC

ERR

OK