ControlLogix ControlNet Interface Module 25

Publication

1756-IN604A-EN-P - February 2006

Red

DUPL
NODE

For a redundant system this may
be a temporary condition during
chassis switchover. Otherwise,
the module’s network address is
the same as another module’s on
the link.

1. (For redundant systems only.)

Wait 10 seconds; if the
condition persists, perform the
following steps:

2. (Optional, see page 12.)

Turn chassis power supply off.

3. Remove the module from the

chassis.

4. Set the network address

switches to a unique address
(01-99).

5. Install the module in the

chassis.

6. If off, turn chassis power

supply on.

RACK
ERR

Cannot read backplane EEPROM,
or rack/slot address incorrect

Replace the chassis.

STOP

The module commanded to stop
functioning by the redundancy
module. This occurs when a
nonredundancy compliant
module is placed into a
redundant secondary chassis.

Remove nonredundancy compliant
module from redundant secondary
chassis and replace with
redundancy compliant module.

WAIT

SRM

(2)

The module waiting for the
redundancy module to complete
power-up.

None required.

Flashing
Red

BOOT

The module has invalid
firmware.

Update module firmware with
ControlFlash Update Utility.

ROM

UPDT

Flash update is in progress.

None required.

SNGL
KPR!

The module detected that it has
been connected to a ControlNet
1.5 (single-keeper) network.

Update the module’s firmware at
MAC ID 01 and reschedule the
network.

Module Status Indicator LED and Module Status Display

LED

Display

Cause

Action

OK