ControlLogix ControlNet Interface Module 29

Publication

1756-IN604A-EN-P - February 2006

Node is not configured to go on
line

Make sure the configuration
manager node is present and
working and selected address is

not greater than selected UMAX

.

(1)

Flashing red/off

Media fault

Check media. For example: broken
cables, loose connectors, missing
terminators.

No other nodes present on
network

Add other nodes to the network.

Flashing red/green Incorrect network configuration

Cycle power or reset unit.

If fault persists, contact A-B
representative or distributor.

(1)

The configuration manager node is the node responsible for distributing ControlNet network
configuration data to all nodes on the network.