Rockwell Automation 1756-CNB ControlLogix ControlNet Bridge Module, Series E Installation Instructions User Manual
Page 31

ControlLogix ControlNet Interface Module 31
Publication
1756-IN604A-EN-P - February 2006
Backplane current
970 mA @ 5.1 V
1.7 mA @ 24 V
Isolation voltage
(continuous-voltage withstand
rating)
50V
Tested to 500V ac for 60 seconds
Wiring category
(1)
2 - on communications ports
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications ControlLogix ControlNet Interface Module
1756-CNB, 1756-CNBR, Series E
Attribute
Value
Operational temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…60 °C (32…140 °F)
Storage temperature
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Operating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Nonoperating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions
CISPR 11:
Group 1, Class A
ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E
Attribute
Value