ControlLogix ControlNet Interface Module 31

Publication

1756-IN604A-EN-P - February 2006

Backplane current

970 mA @ 5.1 V

1.7 mA @ 24 V

Isolation voltage

(continuous-voltage withstand
rating)

50V

Tested to 500V ac for 60 seconds

Wiring category

(1)

2 - on communications ports

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications ControlLogix ControlNet Interface Module
1756-CNB, 1756-CNBR, Series E

Attribute

Value

Operational temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…60 °C (32…140 °F)

Storage temperature

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

2 g @ 10…500 Hz

Operating shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Nonoperating shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A

ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E