Reference – Rockwell Automation 1761 MicroLogix 1000 Programmable Controllers User Manual
Page 321

Valid Addressing Modes and File Types for Instruction Parameters
C–7
Instruction
Description
Instruction
Parameter
Valid Addressing
Mode(s)
Valid File Types
Valid Value
Ranges
HSC
High-Speed Counter
type
immediate
0–7, where:
0=up
1=up&reset/hold
2=pulse/direction
3=pule/direction
& reset/hold
4=up/down
5=up/down &
reset/hold
6=encoder
7=encoder &
reset/hold
counter
direct
C5:0. C5:1
(element level)
Not Applicable
preset
(contained in the
counter register)
–32,768–32,767
accum
(contained in the
counter register)
–32,768–32,767
HSD
HSC Interrupt Disable
counter
direct
C
Not Applicable
HSE
HSC Interrupt Enable
counter
direct
C
Not Applicable
HSL
HSC Load
counter
direct
C
Not Applicable
source
direct
B, N
Not Applicable
length
always 5
IIM
Immediate Input with
slot
direct
I
Not Applicable
Mask
mask
immediate, direct,
indexed direct
O, I, S, B, T, C, R, N
–32,768–32,767
length
immediate
1–10
INT
Interrupt Subroutine
Not Applicable
Reference