Preface

MicroLogix 1000 Programmable Controllers User Manual

D–22

MicroLogix Remote Packet Support

Series D MicroLogix controllers and all MicroLogix analog controllers can respond
to communication packets (or commands) that do not originate on the local DH-485
network. This is useful in installations where communication is needed between the
DH-485 and DH+ networks.

The example below shows how to send messages from a PLC device or a PC on the
DH+ network to a MicroLogix 1000 controller on the DH-485 network. This
method uses an SLC 5/04 processor bridge connection.

When using this method:

•

PLC-5 devices can send read and write commands to MicroLogix controllers.

•

MicroLogix 1000 controllers can respond to MSG instructions received. The
MicroLogix controllers cannot initiate MSG instructions to devices on the DH+
network.

•

PC can send read and write commands to MicroLogix controllers.

•

PC can do remote programming of MicroLogix controllers.

DH

+

Network

PLC-5

SLC 5/04

Modular I/O Controller

DH-485 Network

MicroLogix 1000
Programmable
Controller

MicroLogix 1000
Programmable
Controller

MicroLogix 1000
Programmable
Controller

PLC-5

SLC 5/03 System