Analog voltage and current input and output ranges, Analog voltage input range, Analog current input range – Rockwell Automation 1761 MicroLogix 1000 Programmable Controllers User Manual
Page 57: Analog voltage output range, Analog current output range

Wiring Your Controller
2–23
Analog Voltage and Current Input and Output Ranges
Analog Voltage Input Range
ЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙ
Operating Range
Overrange
Underrange
–10.5V dc
10.5V dc
–24V dc
24V dc
Analog Current Input Range
ЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙ
Operating Range
Overrange
Underrange
–21 mA
21 mA
–50 mA
50 mA
Note
The analog voltage inputs are protected to withstand the application of
24V dc
without damage to the controller. The analog current inputs are protected to
withstand the application of
50 mA without damage.
Analog Voltage Output Range
Operating Range
0V dc
10V dc
Analog Current Output Range
Operating Range
20 mA
4 mA
Note
The analog outputs are protected to withstand the short circuiting of the voltage or
current outputs without damage to the controller.
For information on analog signal and data word values using the nominal
transfer function formula, see page 5–5.