Preface

MicroLogix 1000 Programmable Controllers User Manual

3–8

The table below shows connections for Belden #3106A.

For this Wire/Pair

Connect this Wire

To this Terminal

Shield/Drain

Non-jacketed

Terminal 2 – Shield

Blue

Blue

Terminal 3 – (Common)

White with Orange Stripe

Terminal 4 – (Data B)

White/Orange

Orange with White Stripe

Terminal 5 – (Data A)

The table below shows connections for Belden #9842.

For this Wire/Pair

Connect this Wire

To this Terminal

Shield/Drain

Non-jacketed

Terminal 2 – Shield

White with Blue Stripe

Cut back – no connection

➀

Blue/White

Blue with White Stripe

Terminal 3 – (Common)

White with Orange Stripe

Terminal 4 – (Data B)

White/Orange

Orange with White Stripe

Terminal 5 – (Data A)

➀

To prevent confusion when installing the communication cable, cut back the white with blue stripe wire
immediately after the the insulation jacket is removed. This wire is not used by DH-485.

Grounding and Terminating the DH-485 Network

Only one connector at the end of the link must have Terminals 1 and 2 jumpered
together. This provides an earth ground connection for the shield of the
communication cable.

Both ends of the network must have Terminals 5 and 6 jumpered together. This
connects the termination impedance (of 120

Ω

) that is built into each AIC+ as

required by the DH-485 specification.

End-of-Line Termination

Belden #3106A or #9842 Cable
1219 m (4000 ft) Maximum

Jumper

Jumper

Jumper