Wiring the module, Working with connectors, See the figure that shows connectors – Rockwell Automation 1791ES-IB16 CompactBlock Guard I/O EtherNet/IP Safety Modules  User Manual

Page 11

Advertising
background image

CompactBlock Guard I/O EtherNet/IP Safety Modules 11

Publication

1791ES-IN001C-EN-P - September 2009

Wiring the Module

Follow these guidelines when wiring the module:

Do not route communication, input, or output wiring with conduit

containing high voltage, referring to Industrial Automation Wiring
and Grounding Guidelines, publication

1770-4.1

.

• Wire correctly after confirming the signal names of all terminals.
• Note that stranded wire should be processed with insulation-covered

ferrule (DIN 46228-4 standard compatible-type) at its ends before
using for connection.

• Tighten screws for the power connector correctly at 0.56…0.79 N•m

(5…7 lb•in).

• Tighten screws for the I/O connectors correctly at 0.5…0.56 N•m

(4.5…5 lb•in).

Working with Connectors

See the figure that shows connectors.

Power and EtherNet/IP Connectors

Power Configuration

Pin

Signal

1

Input +24V DC Power

2

Input Power Common

3

Output +24V DC Power

(1)

(1)

NC on 1791ES-IB16 modules.

4

Output Power Common

(1)

EtherNet/IP Connector
8 - No connection
7 - No connection
6 - Receive data minus
5 - No connection
4 - No connection
3 - Receive data plus
2 - Transmit data minus
1 - Transmit data plus

RJ45

8

1

44205

1

2

3

4

Advertising
This manual is related to the following products: