CompactBlock Guard I/O EtherNet/IP Safety Modules 27

Publication

1791ES-IN001C-EN-P - September 2009

Surge transient
immunity

IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM)
on power ports
±1 kV line-line (DM) and ±2 kV line-earth (CM)
on signal ports
±2 kV line-earth (CM) on communication ports

Reaction Time

Input reaction time,
max

16.2 ms + set values of ON/OFF delays

Output reaction time,
max

6.2 ms + (20 ms) relay response time
(1791ES-IB8XOBV4 module only)

Signal Sequence

Environmental Specifications

Attribute

Value

Typ. 600 ms

44072

While safety outputs are in an on state, the signal sequence shown in the figure is
output continuously for fault diagnosis when pulse testing is enabled. Confirm
response time of device connected to safety outputs so the device does not
malfunction due to off pulse.

Typ. 700

μs