CompactBlock Guard I/O EtherNet/IP Safety Modules 17

Publication

1791ES-IN001C-EN-P - September 2009

Flashing
red

Recoverable fault or user-initiated
firmware update in progress

The module has detected a
recoverable fault or user-initiated
firmware update is in progress.

Flashing
red and
green

Device in self test

The module is performing its
power-cycle diagnostic tests.

(1)

For recommended action, refer to the user manual that covers these modules.

Network Status Indicator

(1)

State

Status

Description

Off

Module not online or no power

The module does not have an IP address.

Flashing
green

Module online with no
connections in established state

The module has acquired an IP address,
but no connections are established.

Solid
green

Module online with connections
in established state

The module is operating normally.

Flashing
red

One or more I/O connections in
timed-out state or user-initiated
firmware update in progress

The module detected a recoverable
network fault, I/O connection timed out, or
user-initiated firmware update is in
progress.

Solid red

Critical link failure

The module detected an error that prevents
it from communicating on the network,
such as the Ethernet cable is unplugged.

Flashing
red and
green

Communication faulted module

The module detected a network access
error and is in communication faulted
state. The module received and accepted
an Identity Communication Faulted
Request-long protocol message.

(1)

For recommended action, refer to the user manual that covers these modules.

Module Status Indicator

(1)

State

Status

Description