18 CompactBlock Guard I/O EtherNet/IP Safety Modules

Publication

1791ES-IN001C-EN-P - September 2009

Network Activity Indicator

State

Status

Off

No link established

Flashing green/off

Transmit or receive activity

Steady green

Link established

Safety Input Status Indicator

State

Status

Description

Recommended Action

Off

Safety input
off or module
being
configured

The safety input is off or the
module is being configured.

Turn the safety input on or
wait for the module to be
configured.

Solid
yellow

Safety input
on

The safety input is on.

None.

Solid red

Fault detected

A fault in the external wiring
or input circuit detected.

Check configuration, field
wiring, and devices. If no
problem found, replace
module.

Flashing
red

Partner fault
detected

A fault in the partner input
circuit of a dual input
configuration detected.

Check the field wiring and
verify your configuration for
the partner circuit. If no
problem found, replace
module.