Test Output Status Indicator

State

Status

Description

Recommended Action

Off

Test output off
or module being
configured

The test output
is off or the
module is being
configured.

Turn the test output on or wait for the
module to be configured.

Solid
yellow

Output is on

Output is on.

None.

Solid
red

Fault detected

A fault in the
external wiring
or input circuit
detected.

Check field wiring. If no problem found,
replace module. For outputs configured
for muting could indicate undercurrent or
burned-out lamp.

Safety Output Status Indicator (1791ES-IB8XOBV4 module only)

State

Status

Description

Recommended Action

Off

Safety output
off or module
being
configured

The safety output is off
or the module is being
configured.

Turn the safety output on or wait
for the module to be configured.

Solid
yellow

Safety output
on

The safety output is on.

None.

Solid red

Fault detected

A fault in the output
circuit was detected.

Check the circuit wiring and end
device. If no problem found,
replace module.

Both tags in a dual
channel circuit do not
have the same value.

Make sure logic is driving tag
values to the same state (off or
on).

Flashing
red

Partner fault
detected

A fault in the partner of
a dual output circuit
was detected.

Check the circuit wiring and end
device of the partner. If no
problem found, replace module.