16 ControlLogix DH-485 Communications Module

Publication

1756-IN587A-EN-P - September 2005

Troubleshoot the Power Supply

If the alphanumeric indicator on the 1756-DH485 module does not cycle
through these messages when you turn the power on, refer to the Power
Supply Status tabl
e and to the Troubleshooting section that follows.

Interpret the Alphanumeric Display

Your 1756-DH485 module displays alphanumeric codes that provide
diagnostic information about your module. The alphanumeric display flashes
the codes at approximately one second intervals. Table Alphanumeric Display
Descriptions su
mmarizes the codes.

Power Supply Status

POWER Indicator

Power Supply Status

Recommended Action

Off

Not operating.

Turn power switch ON.

Check power wiring connections.

Check fuse.

On

Operating.

None, normal operation.

Alphanumeric Display Descriptions

Code

Description

Recommended Action

OFF

LINE

DH-485 link is in STOP state.

Correct the configuration.

Refer to the 1756-DH485 User Manual,
publication 1756-UM532.

DUPL

NODE

DH-485 Duplicate node
address.

Choose another node address and reset
switches.

ONLY

NODE

Only node on DH-485 link.

Check the cables.

CNFG

FALT

Incorrect DH-485 routing table
configuration.

Incorrect DH-485 object
configuration.

Correct the configuration. Refer to the
1756-DH485 user manual, pub. 1756-UM532.

Verify the module is inserted in correct slot.