Environmental Specifications
Specification
Value
Operational
Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0...60 °C (32...140 °F)
Storage
Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry
Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating
Thermal Shock):
-40...85 °C (-40...185 °F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp
Heat):
5...95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10...500 Hz
Operating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Non-operating
Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions
CISPR 11:
Group 1, Class A
ESD Immunity
IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges
Radiated RF
Immunity
IEC 61000-4-3:
10 V/m with 1 kHz sine-wave 80%AM from 80...2000 MHz
10 V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
EFT/B Immunity
IEC 61000-4-4:
+/-2 kV at 5 kHz on communications ports