20 ControlLogix DH-485 Communications Module

Publication

1756-IN587A-EN-P - September 2005

Environmental Specifications

Specification

Value

Operational
Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0...60 °C (32...140 °F)

Storage
Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry
Heat),

IEC 60068-2-14 (Test Na, Un-packaged Non-operating
Thermal Shock):

-40...85 °C (-40...185 °F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp
Heat):

5...95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

2 g @ 10...500 Hz

Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Non-operating
Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A

ESD Immunity

IEC 61000-4-2:

4 kV contact discharges

8 kV air discharges

Radiated RF
Immunity

IEC 61000-4-3:

10 V/m with 1 kHz sine-wave 80%AM from 80...2000 MHz

10 V/m with 200 Hz 50% Pulse 100%AM at 900 MHz

EFT/B Immunity

IEC 61000-4-4:

+/-2 kV at 5 kHz on communications ports