Rockwell Automation 1756-DH485 ControlLogix Data Highway 485 Module Installation Instructions User Manual

Page 18

Advertising
background image

18 ControlLogix DH-485 Communications Module

Publication

1756-IN587A-EN-P - September 2005

Set the Network Parameters and Configure the Module

You must use RSLinx software, version 2.43 or later, to set all network
parameters and to configure the 1756DH-485 module.

LED Actions

Channel A or B
Indicator

Channel Status

Recommended Action

Off

Not online.

Place channel online.

Solid Green

Operating.

None, normal operation.

Flashing Green

No other node on the
network.

Check cables.

Solid Red

Hardware fault.

Reboot module. If red reoccurs,
replace module.

Flashing Red

Either:

• Faulted adapters

detected.

• Duplicate node

detected

• Check cables.

Check power at other racks.

• Check node address.

Advertising