Rockwell Automation 1756-DH485 ControlLogix Data Highway 485 Module Installation Instructions User Manual

Page 21

Advertising
background image

ControlLogix DH-485 Communications Module 21

Publication

1756-IN587A-EN-P - September 2005

Surge Transient
Immunity

IEC 61000-4-5:

+/-1 kV line-earth (CM) on communications ports

Conducted RF
Immunity

IEC 61000-4-6:

10 Vrms with 1 kHz sine-wave 80%AM from 150 kHz...80
MHz

Magnetic Field
Immunity

IEC 61000-4-8:

30 A/m at 50 Hz

Enclosure Type
Rating

None (open-style)

Certifications

Certification

Value

Certifications

(when product is marked)

(1)

UL

UL Listed Industrial Control Equipment

CSA

CSA Certified Process Control Equipment

CSA

CSA Certified Process Control Equipment for Class
I, Division 2 Group A,B,C,D Hazardous Locations

CE

European Union 89/336/EEC EMC Directive,
compliant with:

EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial
Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

C-Tick Australian Radiocommunications Act, compliant

with:

AS/NZS CISPR 11; Industrial Emissions

(1)

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and
other certification details.

Environmental Specifications

Specification

Value