Environment and Enclosure
ATTENTION
This equipment is intended for use in a Pollution Degree 2 
industrial environment, in overvoltage Category II applications 
(as defined in IEC publication 60664-1), at altitudes up to 
2000 meters without derating.
This equipment is considered Group 1, Class A industrial 
equipment according to IEC/CISPR Publication 11. Without 
appropriate precautions, there may be potential difficulties 
ensuring electromagnetic compatibility in other environments 
due to conducted as well as radiated disturbance.
This equipment is supplied as “open type” equipment. It must 
be mounted within an enclosure that is suitably designed for 
those specific environmental conditions that will be present and 
appropriately designed to prevent personal injury resulting from 
accessibility to live parts. The interior of the enclosure must be 
accessible only by the use of a tool. Subsequent sections of this 
publication may contain additional information regarding 
specific enclosure type ratings that are required to comply with 
certain product safety certifications.
NOTE: See NEMA standards publication 250 and IEC 
publication 60529, as applicable, for explanations of the degrees 
of protection provided by different types of enclosure. Also, see 
the appropriate sections in this publication, as well as the 
Industrial Automation Wiring and Grounding Guidelines, 
publication 1770-4.1 for additional installation requirements 
pertaining to this equipment.