Table 1 interpreting module and i/o status – Rockwell Automation 1788-CNCR ControlNet Daughtercard Installation Instructions User Manual

Page 15

Advertising
background image

ControlNet Daughtercard 15

Publication 1788-IN002C-EN-P - April 2004

Table 1 Interpreting Module and I/O Status

Indicator

Color

Probable Cause(s)

Recommended Action

Module
Status (MS)

Off

• No power

• Host is faulted

• Host is holding

daughtercard
in reset

• Check the power supply.

• Ensure that the daughtercard is firmly seated in the

slot.

• Cycle power. If the indicator remains off, replace the

daughtercard or the host.

Steady
Red

Major fault

There is a hardware fault with the module. Cycle power.

If the problem persists, replace the daughtercard.

Flashing
Red

• Minor fault

• Firmware

update in
progress

• Node address

switch change

• Invalid module

firmware

• Duplicate node

address

• No action required (firmware update in progress.)

• The daughtercard’s node address switches may have

been changed since power-up. Change the node
address switches back to the original setting. The
module will continue to operate properly.

• Update module firmware with ControlFlash Update

utility.

• The daughtercard’s node address duplicates that of

another device. Remove power, change the node
address to a unique setting, then apply power.

Flashing
Green

No connections
established

No action required.

Steady
Green

Connections
established

No action required.

Flashing
Red/Green

Self-test

The module is performing self-diagnostics. Wait briefly to
see if problem corrects itself.If problem persists, check the
host. If the daughtercard cannot communicate with the
host, it may remain in self-test mode.

I/O Status
(I/O)

Always
Off

This LED is on during the LED portion of the self-tests.