5.0 DIAGNOSTICS AND
TROUBLESHOOTING
This sectiondescribes how to troubleshoot the PC Link module. See
Appendix C for a list of the error codes that can be displayed by the
PC Link module. If the problem cannot be corrected using the
procedures below, the unit is not userĆserviceable.
DANGER
ONLY QUALIFIED ELECTRICAL PERSONNEL FAMILIAR WITH THE
CONSTRUCTION AND OPERATION OF THIS EQUIPMENT AND THE HAZARDS
INVOLVED SHOULD INSTALL, ADJUST, OPERATE, AND/OR SERVICE THIS
EQUIPMENT. READ AND UNDERSTAND THIS MANUAL IN ITS ENTIRETY
BEFORE PROCEEDING. FAILURE TO OBSERVE THIS PRECAUTION COULD
RESULT IN SEVERE BODILY INJURY OR LOSS OF LIFE.
5.1
The Red LED is On and the Green LED is
Off
Problem: The red status LED onthe PC Link module is onand the
greenLED is off. Both LEDs should be onwhenpower to the
personal computer is turned on. Both LEDs should turn off after
either NET.BAT or RIO.BAT is run. An error code signifying the
problem should be displayed on the screen. See Appendix C for
error codes. If the red LED remains on after the problem indicated by
the error code has beencorrected, replace the module.