3 drop register image table (data_table) – Rockwell Automation 57C445 AutoMax PC Link Interface Module User Manual

Page 37

Advertising
background image

D2Ć2

Address

Name

SetBy

Description

000Ć1BFF

DATAąTABLE

BOTH

Drop Register Image Table

1F00Ć1F37

DATAąCHNGE

BOTH

Data Change Table Ć one byte

for each drop. A nonĆzero value

indicates that data for the specifĆ

ic drop has changed.

1F38

STATąCHNGE

BOTH

Status Change Ć Set to 0xFF any

time active drop status changes.

1F39

GLOBąCHNGE

BOTH

Global Change Ć Set to 0xFF

any time STATąCHNGE is set

to 0xFF, or DATAąCHNGE is set

to 0xFF, for drops which are enĆ

abled in the

ENąGLOBąCHNGE table.

1F3A

ENąGLOBąINT

HOST

Enable Global Change Interrupt

1F40Ć1F77

ENąGLOBąCHNG

HOST

Enable Global Change Drop

Table Ć a nonĆzero value for a

particular drop causes

GLOBąCHNGE to be set if

DATAąCHNGE for the given

drop is set.

2.3

Drop Register Image Table (DATA_TABLE)

The Drop Register Image table is divided into 56 drops. Each drop

consists of 128 bytes or 64 registers. Drop register locations can be

calculated using the following formula:

Register_Location = (Drop*128) + (Register*2)

For example, to access Drop 6 register 31, the user would read/write

to:

offset

= (6*128)+(31*2)

= 768+62

= 830 decimal or 0x33E