D3Ć2

Table 3 - RERIO Memory Organization

Address

Name

Set By

Description

0000

MODULEąID

RERIO

Module identification word. Set by REĆ

RIO to 15A1H. Host may use to verify

RERIO software is present.

0400-1FFF

DATAąTABLE

BOTH

Remote I/O data table. Divided into

Drops, Slots and Registers.

2000H

RECONFIG

BOTH

Reconfigure byte. Host sets to 0FFH to

cause card to reĆconfigure using new

information.

2001-2007

VIRąENA

HOST

Virtual drop enable table. Configuration

packet must be present for all drops enĆ

abled in this table. RERIO reads these

values only during

reconfiguration.

2009-200F

PASVąENA

HOST

Passive drop monitor enable table. ConĆ

figuration packet must be present for all

drops enabled in this table. RERIO

reads these values only during reconfiĆ

guration.

2011-2017

VIRąACT

RERIO

Virtual drop active table. Set by RERIO

to indicate that the given virtual rack is

being updated by the Master.

2020

ACTąMAS

RERIO

Set to 0FFH by RERIO whenever an acĆ

tive Master is connected, even if no

drops are enabled.

2021-2027

DROPąACT

RERIO

Drop active table. Set by RERIO to indiĆ

cate that the given rack (virtual or real) is

being updated by the Master.

2100H-27F

F

CNFąBUF

BOTH

Drop configuration buffers. One 256

byte buffer for each drop.

MODULE_ID is a single register which is set to 15A1H by the RERIO

software at install time. The host may read this register to make sure

the RERIO software is present.
The data table (DATA_TABLE) is divided into 7 drops (1-7). Each

drop consists of 16 slots. Each slot consists of 32 registers. This

organization matches the standard Remote I/O configurations with

real remote racks and Remote Heads. Drop/slot/register locations

can be calculated using the following formula:
Register_Location = (Drop*1024) + (slot*64) + (Register*2)
For example to access Drop 6, slot 3, register 7, the user would

read/write to:
offset

= (6*1024)+(3*64)+(7*2)

= 6144+192+14

= 6350 decimal or 0x18CE

RECONFIG is set to OFFH by the host to indicate that the module

should reĆconfigure itself using the current data in the virtual drop

enable table (VIR_ENA), the passive drop monitor enable table

(PASV_ENA), and the drop configuration buffers (CNF_BUF). If the

PC Link module detects a nonĆzero value in this location, it will stop

all virtual drops and stop all updating of passive drop data. The PC

Advertising