D2Ć1

2.0 DCS/AUTOMAX NETWORK

COMMUNICATIONS

(RENET)

Loading the Network Communications software (RENET) onto the PC

Link module enables it to function like a Network Communications

module (M/N 57C404). The PC Link module can act as any valid

drop, except the Master (drop 0), and can have any valid drop depth.

2.1

Differences Between RENET and a

NetworkCommunications Module

The AutoMax Network stores registers in highĆbyte lowĆbyte format,

while the standard for NEC's microprocessors (used on the PC Link

module) is lowĆbyte highĆbyte. The PC Link module automatically

swaps the order of the bytes for all registers in the drop table.
The PC Link module has no way of implementing a read only"

register. This means that no error will be generated if a user writes to

a read only register.
The drop number is written into memory rather than being read from

thumbwheel switches. Status bits 14 and 15 are implemented to

indicate good or bad drop numbers. The drop status bits are

maintained for all active drops, even though the module acts only as

a Slave. These bits only indicate that a given drop is responding to

the Master and do not necessarily reflect valid operation of the drop.

2.2

RENET Memory Organization

The RENET memory is a 16K block starting at offset 0 in the installed

segment. Although 16K is available, not all of it is used. Any

references to module memory in this appendix assume the installed

segment address.
The memory organization of the PC Link module running the RENET

software is summarized in Table 1:

Table 1 Ć RENET Memory Organization