4 data change table (data_chnge), 5 status change flag (stat_chnge) – Rockwell Automation 57C445 AutoMax PC Link Interface Module User Manual

Page 40

Advertising
background image

D2Ć5

2.3.2

Drop 1Ć55 Register Definitions

The register definitions for drops 1Ć55 can be summarized as follows:
Registers 0 through 31 contain 32 words of output (to the Master).

These registers are read/write if the module is actively responding as

this drop; otherwise, these registers are read only.
Registers 32 through 63 contain 32 words of input (from the Master).

These registers are read only.

2.4

Data Change Table (DATA_CHNGE)

The data change table contains one byte for each drop. Drop 0

corresponds to the first location in the table (1f00h). The RENET

software places 0xFF in the data change table for a particular drop

any time data in the drop changes (other than that written by the

host). The data change byte for drop 0 is affected only by changes to

the broadcast data registers (32Ć39).
Rather than poll drops continuously, a host application may check

the DATA_CHNGE flag for a given drop. If it is zero, no data in the

drop has changed and the host may proceed accordingly. If the data

change flag is set to 0xFF, the host then clears the flag to zero, and

reads the updated data for the drop.

2.5

Status Change Flag (STAT_CHNGE)

This flag is set to 0xff by the RENET software if any data in the drop

status registers change (registers 4Ć7 of drop 0). Any change to these

registers indicates that one or more drops have gone on/off line.
Rather than monitor the drop status bits continuously, the host need

only monitor the STAT_CHNGE flag. If it is zero, no drops have gone

on or off line, and the host may proceed accordingly. If the status

change flag is set to 0xFF, the host then checks the relevant bits in

the drop status registers (registers 4Ć7 of drop 0).

2.6

Global Change Flag (GLOB_CHNGE) and

Enable Global Change Table

(EN_GLOB_CHNGE)

The Global Change flag is used in conjunction with the Enable

Global Change Drop Table to provide a flag which is set only when

data in selected drops changes. The global change flag will also be

set if the status changes (See section 2.5 of this appendix).
For example:
A particular application needs only to monitor drops 0, 3, and 7.
The host places 0xff in the EN_GLOB_CHNGE table for drops 0, 3,

and 7 at locations 0x1F40, 0x1F43, and 0x1F47. The GLOB_CHNGE

flag will be set any time data in any of the given drops changes.
The host needs to monitor the GLOB_CHNGE flag only. If it is set, the

host clears it to 0. The host then checks the status change flag and

the data change flags for the given drops and proceeds accordingly.