Troubleshooting

The LED provides status information on RediSTATION operations.
The LED is visible when the enclosure cover is removed.

The troubleshooting chart shows LED indications. It also shows
how to use the LED to detect and correct common operating
problems.

LED

Wh

s

Wh

Color

State

What it Means:

What to do:

None

1. RediSTATION is not receiving input power.

1. Check DeviceNet power and cable

connections and the power connection on the
DeviceNet terminal block. Page 3 references
this connection.

Red

Solid

1. Diagnostics failed on powerup/reset.

2. DIP switch settings changed after powerup.

DIP Switch settings are only read during a
powerup/reset.

3. Over–temperature error detected during

runtime. Outputs turn off.

4. Invalid data rate.

1. Internal fault. Reset device. If fault still

exists, return RediSTATION for repair.

2. Power down RediSTATION. Set DIP switch

settings. Reconnect power.

3. Check ambient temperature rating. Reset

device.

4. Reset DIP switches 7 and 8 to a valid

DeviceNet data rate. See page 5 for valid
data rates and cable lengths. Reset device.

Red

Flashing

1. Duplicate DeviceNet node address. Two

nodes cannot have the same address.

2. Pilot light lamp is burnt out – open circuit on

output.

3. Pilot light is not wired correctly to the I/O

connector or the screw terminals of the
device – short circuit/overload.

4. I/O connection timeout.

1. Reset DIP switches 1 through 6 using a valid

address. Page 4 provides a table of
possible address settings. Reset device.

2. Replace pilot lamp bulb.

3. Check I/O cable connections for the pilot light

device.

4. Reset device.

Green

Solid

1.

Normal operating state and device is
allocated to a master device.

1. No action required.

Green

Flashing

1.

Device is online but not allocated to master.

2. Device is in idle state.

1. Check DeviceNet master for correct

RediSTATION configuration information (node
address, input bytes, output bytes).

2. Check DeviceNet master for proper

operation.

The LED does not indicate the following malfunctions.

Problem

What it Means:

What to do:

Switch or button operators
do not function

1. Loose wiring

2. Incorrect address

3. Faulty contacts, switch or button

1. Check wiring and cable connections.

2. Check address setting of the DIP switch.

3. Use an ohmmeter to verify opening/closing of

contacts.

Using the LED Indicator