4

Installation and Mounting

The setting of the DIP switch on the circuit board determines:

DeviceNet node address

DeviceNet data rate

Output flash rate

Output fault state

The location of the DIP switch and the factory defaults are shown
below.

DIP Switches

OFF = 0

ON = 1

10

1

2

3

4

5

6

7

8

9

Setting the DeviceNet Node Address

DIP switches 1 to 6 set the node address (0 to 63) of the
RediSTATION on the DeviceNet network. The address is set using
binary addressing.

DeviceNet Address

000000 – 111111 (0 to 63)

OFF = 0

ON = 1

10

1

2

3

4

5

6

7

8

9

The table below shows the switch settings for each address (0 to 63).

To set the DeviceNet node address:

1. Refer to the table below for switch settings of a specific address.

2. Using your finger or a pointed object, slide switches 1 through 6

to the appropriate ON/OFF positions.

!

ATTENTION: Do not use a pencil. Graphite from the pencil
is conductive and may damage the DIP switch.

Setting the DIP Switches

Advertising