Devicenet termination, Setting the output fault state, Setting the output flash rate – Rockwell Automation 2705-DN42 DeviceNet Interface Communicaton Board User Manual

Page 6

Advertising
background image

6

Setting the Output Fault State

DIP switch 9 sets the state of the outputs (pilot lights) when the
device detects an error. The factory default setting is to turn the
outputs off when an error is detected.

Output Fault State

0 = Outputs Turn Off on Fault
1 = Outputs Hold Last State on Fault

Default Configuration

OFF = 0

ON = 1

10

1

2

3

4

5

6

7

8

9

Output Fault States

Description

Outputs Retain Last State

When communications is lost, the station stops sending sig-
nals. The station ignores push button presses in the error
state. The outputs remain in their last state.

Outputs Turn Off on Error

When communications is lost, the station turns off outputs. The
station ignores push button presses in the error state. When
communications is regained, the station updates itself and
resumes operations.

To change the fault state, slide switch 9 to the appropriate ON/OFF
setting.

Setting the Output Flash Rate

DIP switch 10 sets the flash rate of the outputs (pilot lights). The
factory default setting is 1 Hz.

Output Flash Rate

0 = 1 Hz (0.5 sec On, 0.5 sec Off)
1 = 2 Hz (0.25 sec On, 0.25 sec Off)

Default Configuration

OFF = 0

ON = 1

10

1

2

3

4

5

6

7

8

9

To change the flash rate, slide switch 10 to the appropriate ON/OFF
position.

Devices on end nodes of the DeviceNet network require termination.
If the RediSTATION is an end node, you must provide network
termination.

To terminate the RediSTATION, install a 121 ohm 1% metal film
resistor between the CAN_High and CAN_Low terminals on the
DeviceNet terminal block.

DeviceNet Removable
Terminal Block

CAN_Low

CAN_High

DeviceNet Termination

Advertising