Overview, Led indicator, Dip switches – Rockwell Automation 2705-DN42 DeviceNet Interface Communicaton Board User Manual

Page 2: Led indicator dip switches

Advertising
background image

2

Overview

The RediSTATION has one bicolor LED (red/green) to show its
operating status. The LED shows the following indications.

Color

State

Indication

None

Off

No power.

Solid

Unrecoverable fault.

Red

Flashing

Output error or configuration error.

Green

Solid

Normal runtime operation.

The RediSTATION device is operating as a slave to
the master controller.

Flashing

Device is idle or not allocated to a master.

The LED is visible when the cover of the enclosure is removed.

The RediSTATION has one 10-position DIP switch for setting:

DeviceNet Node Address

DeviceNet Data Rate

Output Fault State (Off or Last State)

Output Flash Rate

The DIP switch is located on the circuit board inside the enclosure.
The switch settings and functions are shown below. The default
setting for each switch or group of switches is underlined.

Default Configuration

OFF = 0

ON = 1

Output Fault State

0 = Outputs Turn Off on Fault
1 = Outputs Hold Last State on Fault

DeviceNet Address

000000 – 111111 (0 to 63)

10

1

2

3

4

5

6

7

8

9

Output Flash Rate

0 = 1 Hz (0.5 sec On, 0.5 sec Off)
1 = 2 Hz (0.25 sec On, 0.25 sec Off)

DeviceNet Data Rate 00 = 125K BPS

01 = 250K BPS
10 = 500K BPS
11 = Invalid

LED Indicator

DIP Switches

Advertising