The Allen-Bradley 1747-SDN and 1771-SDN DeviceNet Scanner
Modules are master devices on the DeviceNet network. The
RediSTATION supports the Master/Slave Connection Set for
master/slave communications on the DeviceNet network.

To communicate with a RediSTATION, the DeviceNet Scanner
Module must be configured with the RediSTATION:

node address

input bytes (1)

output bytes (1)

The DeviceNet Scanner Module:

connects to the RediSTATION slave device

performs the appropriate connection configuration

polls the RediSTATION for inputs and outputs

Response Times

The RediSTATION responds to a DeviceNet Scanner poll within 1
millisecond.

The switch inputs are debounced for 50 milliseconds. When a
change of state is detected, the inputs are not read for another 50
milliseconds.