Operations

The RediStation has 3 modes of operations:

Powerup / Reset mode

Run mode

Error mode

Powerup/Reset Mode

During a powerup or reset, the RediSTATION:

1. Clears outputs (turns outputs off) and sets the LED indicator to

solid red.

2. Performs powerup diagnostic tests including:

EPROM checksum test

RAM read/write test

Watchdog timer test

Serial number verification

If any test fails, the outputs remain off and the LED remains solid
red. You must cycle power to recover from a power-up
diagnostic test failure. Repeated failures indicate a faulty unit.

3. Reads and stores the DIP switch settings.

Important: DIP switches are only read in powerup or reset
mode. Changes to DIP switch settings under power cause an
error.

4. Performs a duplicate node address check to verify that another

node is not assigned the same DeviceNet address as the
RediSTATION device.

If a duplicate node error occurs, the outputs turn off and the status
led is set to blinking red. You must cycle power to clear the error.

During a powerup or reset, the LED is red. If the powerup or reset is
successful, the RediSTATION enters run mode and the LED flashes
green.

Run Mode

After a successful powerup or reset, the RediSTATION enters run
mode and operates as a slave device to a master device. In run
mode, the:

controller scans switch inputs and writes lamp outputs.

station accepts output messages and poll messages from other
nodes on the DeviceNet network.

station monitors outputs for underloads/overloads.

Modes of Operation