Setting the data rate – Rockwell Automation 2705-DN42 DeviceNet Interface Communicaton Board User Manual

Page 5

Advertising
background image

5

DeviceNet

Address

Switch Settings

6

z 1

DeviceNet

Address

Switch Settings

6

z 1

DeviceNet

Address

Switch Settings

6

z 1

DeviceNet

Address

Switch Settings

6

z 1

0

000000

16

010000

32

100000

48

110000

1

000001

17

010001

33

100001

49

110001

2

000010

18

010010

34

100010

50

110010

3

000011

19

010011

35

100011

51

110011

4

000100

20

010100

36

100100

52

110100

5

000101

21

010101

37

100101

53

110101

6

000110

22

010110

38

100110

54

110110

7

000111

23

010111

39

100111

55

110111

8

001000

24

011000

40

101000

56

111000

9

001001

25

011001

41

101001

57

111001

10

001010

26

011010

42

101010

58

111010

11

001011

27

011011

43

101011

59

111011

12

001100

28

011100

44

101100

60

111100

13

001101

29

011101

45

101101

61

111101

14

001110

30

011110

46

101110

62

111110

15

001111

31

011111

47

101111

63

111111

Setting the Data Rate

DIP switches 7 and 8 set the data rate at which the RediSTATION
communicates on the DeviceNet network. The factory default
setting is 125K BPS.

DeviceNet Data Rate

00 = 125K BPS
01 = 250K BPS
10 = 500K BPS
11 = Unused

Default Configuration

OFF = 0

ON = 1

10

1

2

3

4

5

6

7

8

9

The data rate determines the maximum length of the DeviceNet
cable.

Data Rate

Cable Length (Maximum)

125K BPS

500 meters (1600 feet)

250K BPS

200 meters (600 feet)

500K BPS

100 meters (300 feet)

To set the DeviceNet data rate:

1. Refer to the table above to select the correct data rate.

2. Slide switches 7 and 8 to the appropriate ON/OFF positions.