Set the ground jumper, Jumper/wire location and removal instructions – Rockwell Automation 2099-BMxxx Kinetix 7000 High Power Servo Drive Installation Instructions User Manual

Page 5

Advertising
background image

Kinetix 7000 High Power Servo Drives 5

Rockwell Automation Publication 2099-IN003B-EN-P - August 2013

Set the Ground Jumper

Use the following table and illustrations to set the ground jumpers/wires for ungrounded power.

Jumper/Wire Location and Removal Instructions

Remove the Ground Wires on 2099-BM06-S, 2099-BM07-S, and 2099-BM08-S Drives

The common mode capacitor jumper is indicated by callout 1 (PE A) and the MOV jumper is
indicated by callout 2 (PE B).

Drive Cat. No.

Jumper/
Wire

Callout No.

Component
Protected

Description

2099-BM06-S
2099-BM07-S
2099-BM08-S

PE A

Common mode
capacitor

Remove the two jumpers above the power terminal
block. Refer to

Remove the Ground Wires on

2099-BM06-S, 2099-BM07-S, and 2099-BM08-S Drives
on page 5

.

PE B

MOVs

2099-BM09-S
2099-BM10-S

Green/yellow
wire

Common mode
capacitor

Remove DC-DC converter and drive top cover, and
disconnect the green/yellow wire from the drive
chassis. Insulate and secure the wire to prevent
unintentional contact with the chassis or components.
Refer to

Remove the Ground Wires on 2099-BM09-S

and 2099-BM10-S Drives on page 6

.

MOVs/
input filter cap

Disconnect the green/yellow wire next to the power
terminal block. Insulate and secure the wire to prevent
unintentional contact with the chassis or components.
Refer to

Remove the Ground Wires on 2099-BM09-S

and 2099-BM10-S Drives on page 6

.

2099-BM11-S
2099-BM12-S

Green/yellow
wire

Common mode
capacitor

Disconnect the two green/yellow wires from the PE
terminals on the power terminal block. Insulate and
secure each of these wires to prevent unintentional
contact with the chassis or components. Refer to

Remove the Ground Wires on 2099-BM11-S and
2099-BM12-S Drives on page 6

.

MOVs

1

2

3

4

5

6

BR1 BR2 DC+ DC- U/T1 V/T2 W/T3 R/L1 S/L2

T/L3

PE B

PE A

75C Cu Wire

3 AWG [25MM

2

] Max.

16 IN. LBS.
1.8 N-M

} TORQUE

WIRE
STRIP

CONTR

OL

PO

WER

AUX IN

+ –

SHLD

SHLD

PE

75C Cu Wire

6 AWG [10MM2] Max.

BR1 BR2

12 IN. LBS.
1.4 N-M

} TORQUE

PE A

PE B

CM Cap

MOV

Two Jumpers
PE A and PE B

Important: Do not discard or replace the grounding hardware.

1