6 Kinetix 7000 High Power Servo Drives

Rockwell Automation Publication 2099-IN003B-EN-P - August 2013

Remove the Ground Wires on 2099-BM09-S and 2099-BM10-S Drives

The common mode capacitor ground wire is indicated by callout 3 and the MOV/input filter
cap ground wire is indicated by callout 4.

Remove the Ground Wires on 2099-BM11-S and 2099-BM12-S Drives

The common mode capacitor ground wire is indicated by callout 5 and the MOV ground wire is
indicated by callout 6.

IMPORTANT

You must remove the DC-DC converter and drive top cover to access and remove the common
mode capacitor ground wire. Refer to the Kinetix 7000 DC-DC Converter and Control Board
Kits Installation instructions, publication

2099-IN002

.

WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

CM Cap - Older Drives

CM Cap - Newer Drives

MOV

MOV/Input

Filter Cap

3

3

4

4

U

T1

V

T2

W

T3

R

L1

S

L2

INPUT

OUTPUT

T

L3

PE

PE

PE

PE

MOV

CM Cap

DO NOT REMOVE