PanelView 1000 Terminals 11

Publication 2711-IN036J-EN-P - November 2009

1. Secure the base of the retainer over the existing memory card slot using the 2 screws

provided. Tighten screws to a torque of 0.7…0.9 N

m (6 …8 lb•in).

2. Insert the memory card and install the retainer until it is properly seated.

3. To remove the retainer, press the tabs on each side and pull.

Connecting AC Power

Below are AC electrical ratings for the PanelView 1000 terminals.

The PanelView 1000 terminal is an EN/IEC 61131-2 Equipment Class I device and requires

you to connect the

(Protective Earth) terminal to an earth conductor.

Terminal Type

Supply Voltage

Power Consumption

PV1000G and PV1000C

85…264V AC, 47…63 Hz

55VA maximum

ATTENTION

The terminal is designed for safe use when installed in a suitably rated NEMA Type 12,
13, 4X (indoor use only), IP54 or IP65 enclosure.

ATTENTION

Do not apply power to the terminal until all wiring connections have been made. Failure
to do so may result in electrical shock.

ATTENTION

Explosion Hazard - Do not connect or disconnect equipment while circuit is live unless
area is known to be non-hazardous.