Connecting AC Power
Below are AC electrical ratings for the PanelView 1000 terminals.
The PanelView 1000 terminal is an EN/IEC 61131-2 Equipment Class I device and requires
you to connect the
(Protective Earth) terminal to an earth conductor.
Terminal Type
Supply Voltage
Power Consumption
PV1000G and PV1000C
85…264V AC, 47…63 Hz
55VA maximum
ATTENTION
The terminal is designed for safe use when installed in a suitably rated NEMA Type 12,
13, 4X (indoor use only), IP54 or IP65 enclosure.
ATTENTION
Do not apply power to the terminal until all wiring connections have been made. Failure
to do so may result in electrical shock.
ATTENTION
Explosion Hazard - Do not connect or disconnect equipment while circuit is live unless
area is known to be non-hazardous.