Hazardous location considerations – Rockwell Automation 2711-PV1000 PanelView 1000 Terminals User Manual

Page 5

Advertising
background image

PanelView 1000 Terminals 5

Publication 2711-IN036J-EN-P - November 2009

Route incoming power to the PanelView terminal by a separate path from the
communication cable.

Where power and communication lines must cross, they should cross at right angles.
Communication lines can be installed in the same conduit as low level DC I/O lines
(less than 10 Volts).

Grounding minimizes noise from electromagnetic interference (EMI) and is a safety
measure in electrical installations. To avoid EMI, shield and ground cables
appropriately.

A source for grounding recommendations is the National Electrical Code published
by the National Fire Protection Association of Boston.

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D; Class II, Division
2, Groups F and G; Class III; or non-hazardous locations only. The following WARNING

statement applies to use in hazardous locations.

See the nameplate on terminal for hazardous locations certifications.

WARNING

EXPLOSION HAZARD

Substitution of components may impair suitability for Class I, Class II, Class III.

Do not replace components or disconnect equipment unless power has been
switched off or the area is known to be non-hazardous.

Do not connect or disconnect components unless power has been switched off
or the area is known to be non-hazardous.

This product must be installed in an enclosure. All cables connected to the
product must remain in the enclosure or be protected by conduit or other means.

All wiring must comply with N.E.C. article 501-4(b), 502-4(b), 503-3(b) as
appropriate.

ATTENTION

In Class I, Class II, Class III Hazardous locations, the PanelView terminal must be
wired per the National Electric Code as it applies to hazardous locations. Peripheral
equipment must also be suitable for the location in which it is installed.

Advertising