Connecting dc power – Rockwell Automation 2711-PV1000 PanelView 1000 Terminals User Manual
Page 13

PanelView 1000 Terminals 13
Publication 2711-IN036J-EN-P - November 2009
Connecting DC Power
The L1 versions (Catalog No. 2711-T10G1L1) of the PV1000 terminals connect to a 24V DC
power source.
The electrical ratings for the PanelView 1000 terminals is shown below. Electronic circuitry
and an internal fuse protect the terminals from reverse polarity and over-voltage conditions.
To connect DC power to the PV1000 terminal:
1. Secure the DC power wires to the DC negative and DC positive screws on the
terminal block.
2. Secure the Earth Ground wire to the screw on the terminal block.
Terminal Type
Supply Voltage
Power Consumption
PV1000G
18…32V DC, (24V DC nominal)
24 Watts max. (1.0 Amps @ 24V DC)
PV1000C
18…32V DC, (24V DC nominal)
24 Watts max. (1.0 Amps @ 24V DC)
ATTENTION
Do not connect the PanelView terminal to an AC power source. Connecting to an AC
power source may damage the terminal.
ATTENTION
The PanelView terminal is designed for safe use when installed in a suitably rated NEMA
Type 12, 13, 4X (indoor use only), IP54 or IP65 enclosure.
ATTENTION
Explosion Hazard - Do not connect or disconnect equipment while circuit is live unless
area is known to be non-hazardous.