Kinetix 6000M Integrated Drive-Motor Power Interface Module 11

Publication 2094-IN016A-EN-P - February 2012

Safe-off Connector

Each IPIM module ships with the wiring-plug
header and motion-allowed jumper installed in the
Safe-off Connector. With the jumper installed, the
safe-off feature is not used.

This connector extends the safe-off signals for use in
wiring single and multiple safe-off drive
configurations, or to jumper around (not use) the safe-off feature. Refer to the Integrated
Drive-Motor System User Manual, publication

2094-UM003

, for further information.

Enable Input

One digital input is supplied to enable all connected IDM units. The enable
status is transmitted to all of the IDM units through the CAN bus.

Terminal

Description

Signal

Strip
Length
mm (in.)

Torque

N•m (lb•in)

Min/Max
Wire Size

(1)

mm

2

(AWG)

(1)

Maximum/minimum that the connector will accept—these are not recommendations.

1

Feedback Monitoring 2+

FDBK2+

F2+

7.0 (0.275)

0.235 (2.0)

0.14…1.5
(30…14)

2

Feedback Monitoring 2-

FDBK2-

F2-

3

Feedback Monitoring 1+

FDBK1+

F1+

4

Feedback Monitoring 1-

FDBK1-

F1-

5

Safety Enable Input 2

SAFETY ENABLE2+

SE2

6

Safety Enable Common

SAFETY ENABLE-

SE-

7

Safety Enable Input 1

SAFETY ENABLE1+

SE1

8

Safety Bypass Supply, +24V DC,
320 mA max

24+

24+

9

Safety Bypass supply, Common

24V COM

24-

Terminal

Description

Signal

Strip Length

mm (in.)

Torque

N•m (lb•in)

Min/Max
Wire Size

(1)

mm

2

(AWG)

(1)

Maximum/minimum that the connector will accept—these are not recommendations.

1

+24V DC Enable Supply

ENABLE 24V+

+

7.0 (0.275)

0.235 (2.0)

0.14…1.5
(30…14)

2

Enable Input

ENABLE INPUT

EN

3

24V DC Common

ENABLE 24V COM

-

1

F2+

F2-

F1+

F1-

SE2

SE-

SE1

24+

24-

Motion-allowed Jumper
(not installed)

Wiring Plug Header

1

+

EN

-