background image

Kinetix 6000M Integrated Drive-Motor Power Interface Module 9

Publication 2094-IN016A-EN-P - February 2012

Wiring

Interconnecting the IPIM Module and IDM Units

A hybrid cable, catalog number 2090-CHBIFS8-12AA

xx, transfers DC bus power and

inter-module communication signals from the IPIM module to the first IDM unit. Additional
IDM units are daisy chained by using a 2090-CHBP8S8-12AA

xx cable as shown in

IPIM and

IDM Interconnect

on

page 3

.

The IDM system network is routed by using
2090-CNS

xPxS-AAxx cables. A 2090-CNSSPRS-AAxx

or 2090-CNSSPSS-AA

xx cable is required for connection

to the IPIM module.

When installing network cables, torque the connector plug to 0.8…1.2 N•m (7.1…10.6 lb•in) to
fully seat the contacts and secure the connection.

ATTENTION: To avoid personal injury and/or equipment damage, make sure that installation
complies with specifications regarding wire types, conductor sizes, branch circuit protection, and
disconnect devices. The National Electrical Code (NEC) and local codes outline provisions for safely
installing electrical equipment.

42- (white/blue)
42+ (blue)

CN- (blue)
CN+ (white)
SH2 (drain)

RTN (pink)
OUT (white/pink)
SE1 (orange)
SE2 (yellow)
SE- (violet)
SH3 (drain)

DC+ (brown)
PE (green)
DC- (grey)

DC+