Chapter 2 Installation

Mounting Clearances

When selecting an installation site for the computers, be sure to allow adequate
clearance on the sides and rear of the computer for proper ventilation, cable
connection, and hardware access. Sufficient airflow throughout the system unit is
required to maintain proper cooling. Clearance should be enough to allow
convenient installation or removal of peripheral components, such as the
CompactFlash card.

IMPORTANT

Use adequate ventilation or other cooling methods to maintain the
product temperature at its specified rating.

Because of self-heating, do not operate the computer in an enclosure by
using the minimum clearances unless adequate ventilation or other
cooling methods are used to lower the temperature within the enclosure.

The minimum required enclosure size (HxWxD) is 403 x 497 x 154 mm
(15.87 x 19.57 x 6.06 in.).

Item

Description

Value

1

Top

50 mm (2 in.)

2

Back

50 mm (2 in.)

3

Left (for airflow)

50 mm (2 in.)

4

Right (for airflow and drive access)

127 mm (5 in.)

5

Bottom (for I/O port access and ventilation)

102 mm (4 in.)